E L S E V I E R Energy and Buildings 22 (1995) 91-99

ENE&GY j.M ID BUII.,.DING5

Performance studies of a passively cooled mahal

G.N. Tiwari a, N. Lugani a, A.K. Singh u, H.P. Garg

a

= Centre for Energy Studies, Indian Institute o f Technology Delhi, Hauz Khas, New Delhi 110016, India b Development Alternatives, B-32 Tara Crescent, Qutal Institutional Area, New Mehrauli Road, New Delhi 110016, lndia

Received 1 March 1994; accepted 15 June 1994

A b s t r a c t

The design and performance of an ancient passively cooled mahal (building) have been presented. The mahal was generally used for pilgrims during their visit to the city of Banaras. Energy balance equations for different components, namely walls and roof, of a mahal have been used to evaluate the performance of the mahal in terms of an enclosed-room air temperature.

It is observed that a reasonable thermal comfort temperature is achieved by ventilation using natural cold air through the windows.

Keywords: Passive building; Natural cooling; Design; Solar house

1. Introduction

In order to achieve thermal comfort in the environ- ment inside a building, various cooling and heating concepts have been classified as (i) passive concepts, and (ii) active concepts.

In the passive concept, cooling and heating devices are integrated into the building. If the cooled/heated air is forced to pass inside the building to achieve thermal comfort from external conditions, then it is referred to as an active concept.

Various passive cooling techniques are available in the literature [1,2]. Some of these techniques are as follows:

(i) evaporative cooling [3,4];

(ii) shading effect [5];

(iii) mud/stone walls [6,7];

(iv) ventilation/infiltration [8].

In this paper, an old building known as Raja mahal, used for religious services, has been studied to see the effect of various cooling concepts considered before construction. The Raja mahal is situated near the banks (ghat) of the River Ganges in Banaras (a city in the state of Uttar Pradesh in India, Fig. 1), now known as Varanasi. Most of the passive cooling concepts were preserved during renovation of the building. The per- formance of the building has been studied using the basic energy balance for each component of the building including the effect of natural cooling/ventilation and evaporative cooling. Some innovative concepts such as an existing underground tunnel can be integrated for further cooling purposes.

0378-7788/95/$09.50 © 1995 Elsevier Science S.A. All rights reserved SSDI 0 3 7 8 - 7 7 8 8 ( 9 4 ) 0 0 9 0 6 - Z

r/SRINAGAR ,."

.LE~ J I~.JAMM U 1

PAK ISTAN r" [ ~>"~'.~,

r,. t"

°DELHI ~ ' x . A / ~ ' ~ ' ~ . ~ ~ / ~ . . . J ~

/ ^ ' ~ ' / '~.x. ~.,.~ • . . . . C. '~

C .JAfPUR" K~R.'LUCK~0W ... ,'~ ... ' ;

".\ JODHPUR~ BANoARAS. PAT NA d" ~"~. ".. /s

f\ C -.: ,

xx~J~ I N D I

A ~ k

BOMBAYI0 BAY

ARABIAN ~ " .¢" B E N G A L /. J

SEA ~ ~ ~ "

oo~\~ I- ~....

I N D I A N O C E A N

Fig. l. Geographical location of Banaras city.

From numerical computations, it has been inferred that:

(2)

92 G.N. Tiwari et al. / Energy and Buildings 22 (1995) 91-99

(i) there is an improvement in thermal comfort by using natural ventilation through the windows;

(ii) thermal comfort can be further increased by having evaporative cooling.

2. Historical background of Banaras

Banaras, an urban area in India (Fig. 1), originated as a site of pilgrimage, and became a centre for the transformation of silk and a leading market in the north Indian financial network.

The founding date of the original city of Banaras is uncertain and the debate between archaeologists and traditional historians concerning the emplacement of Banaras remains open. Jain historical sources mention the visit of (King) Ashoka in 240 BC, Buddha in the 6th century and the birth of Parasvanath in Banaras in the 8th century. Traditional historians argue that the traditional Banaras region has remained unchanged since the founding of the city [9].

As with other ancient Indian cities, Banaras developed through an urban sequence as follows:

(i) the distinctive urban fabric, situated in the part of the city which was at one time called Pakka and nowadays Cauk;

(ii) the urban development spread along the river, composed of representative buildings of the states of Hindu princes;

(iii) the surrounding districts emerged.

The built-up city is segregated by the ghat (vast beaches of stones), pavements and landings ensuring passage towards the water of the River Ganges. They were erected during the construction of the palaces and the bank buildings. They ensure transitional spaces which were developed continuously along the left shore of the River Ganges and accommodate numerous ac- tivities of Banarasi culture. They ensure free access to pilgrims and to the public [10].

Permitting frontal access to the water, the ghats are extended by pavements which permit access to the building situated on the upper edge. The projecting facade (front elevation of the building) on the supporting wall, appears to be imposed and prevents the building from flooding during the monsoon season.

3. Details of Raja mahal 3.1. General description

Access to the refectory is by way of a stairway leading from the ghat and passing under the Naubat (the place where the priest plays the trumpet). The refectory is a two-storey building with a terrace roof. On each floor there are a kitchen, a store room and a large hypostyle hall (hall with a large number of columns). Each floor is lit by a central square courtyard. In 1980 the building was restored, using traditional techniques, by the Indian National Trust for art cultural heritage.

3.2. Building plan

The square building faces the River Ganges on the east side (Fig. 2(a) and (d)) and is 19 m away from the river. The main hypostyle is 18.29 m × 18.49 m. It has two bays 9.14 m wide on all sides (as shown by dotted lines in Fig. 2(a) and (b)). Each side has 9 columns of 0.7 m × 0 . 5 m. The central four columns are closely spaced. Along the main hall towards the south there are three rooms measuring 3.0 m × 5.8 m, 3.0 m × 5.8 m and 8.7 m × 4.3 m. These rooms are used for grain storage on the ground floor and as a kitchen, on the first floor (Fig. 2(b)) to serve food to the Brahmins.

On the north side there is a small temple.

The central courtyard always had a large cylinder- like vessel in which water was stored from the River Ganges. There is no well in the building unlike other buildings along the ghat.

The window openings are on the east side of the building towards the river bank. The windows are provided only on the first floor (Fig. 2(b)) of the Raja mahal at a sill level of 2.5 m above floor level. The size of the windows is 0.6 m × 0 . 6 m. The window sections are inset in a 1.0 m thick stone wall. They are thirteen in number placed at the refectory level on the first floor (Fig. 2(b)). The entrance to the first floor is by the stairway, 2.1 m wide, which leads to the hypostyle hall.

The frame of wooden beams and purlins (wooden members to support the roof) supports the roof of 0.3 m thickness of lime mortar. The wooden beam sections have now been replaced by 'I' sections of steel, over which a concrete roof of 0.4 m of cement mortar in a 1:2:4 cement-mortar mix has been laid. The building is at a plinth level of 11.6 m from the water level (Fig.

2(c)). The plinth is assumed to be resting on a foundation filled with stone boulders compactly laid together with mortar. The hypostyle hall on the first floor leads to the terrace at the ground-floor hall. The terrace over- looks the River Ganges.

The building under study is known as Raja mahal which consists of a terrace on which there is a refectory (where pilgrims are served food) reserved exclusively for the Brahmins (a caste in Hindu religion), temples and a residential building.

4. Natural cooling concepts

The effects of air temperature, solar radiation, hu- midity, wind and sky clearness upon the building de- termine the internal thermal environment. These out-

(3)

i

-- ~;I~ ,i li ii ii ,', Iii i Ii

~11/.:. < I~~A_;_;_. ... ~Jil

irE:O] ][[D[]][ ... I 'I I ! Ill I i

~ :~, II

....

,,'I ll! il '!, f t !t=il -II

l I ... ~ ' I , I ... ,

If": '!-'

" " I I I" ,t'Zl I i~iI! :''1, . k I I~ < ... 'A., ~ ,', ! , ____ .... ' ... "-I' ' ' ~ " r.~

i ~~~_,_~

it~o 7A_~<: I ~_~, "----" ;,~ ... el ii ILL-- _-zli-" i II Ii ! ' ' '~ , h I, i i ;1/ ,: ii / kT~l[" ' ~' ' .... ill ' - ... -~r ~- ... J[- ... ~i :', i! i" ~i '," ... -~i LJ ~LCONY ... ~ .... ~_.

7.2~M R AJA .... 4, .... Ii.a :~ ,~ ,, ,i~-.,>---~~-.___-- ---...~. > Z

G ANC, A RWER

(4)

94 G.N. Tiwari et aL / Energy and Buildings 22 (1995) 91-99

(c)

STREET LEVEL

~ 21.~M

i 7 ~ r ~ . . . i l l _ . F I R S T FLOOR LEVEL + 1 5 . S M

GROUND FLOOR LEVEL .11.6M

.- - F ~ J A [ " - - " ' ' L -

... " 'i,:[ 5

. ' : SIKRAUL , ' ' ADAMP ',

'" "'" "', CHAITGAN J ' 6 ~ 7

F- ' h r ' - -

" " / , ' ~ 4"" 9 - ~ - - . , 1 0 / I

:" ' DASASHWAMEDH F - . j / I G.\"

,' I AJAs M~/BAL /

(~', ,' I I IRAJA GHAT

' BHELUPURA /

(d)

?

Fig. 2. (a) Ground-floor plan of Raja mahal. (b) First-floor plan of Raja mahal. (c) Sectional elevation of Raja mahal.

door conditions are constantly changing and, at any given time, their effects on a specific building element depend upon the location and orientation of that ele- ment. Solar radiation is the main cause of overheating of buildings. Therefore, reduction of solar radiation, interception, absorption and inward transmission by the building envelope are the first principles for natural cooling [5,7]. T h e solar radiation received by the building elements is d e p e n d e n t on their orientations.

T h e variation of solar intensity on the horizontal and east surface wall is shown in Fig. 3. Direction of air and wind in general is in the south-west to north-east direction. The wind velocity in summer varies between 2 and 2.5 m/s. The main component of solar radiation is on the roof and the wall facing the south-east direction.

O t h e r walls are overshadowed by adjacent buildings along the street. O t h e r exposed surfaces b o r d e r the alley (narrow street). The most favourable orientation is therefore south-east.

Structural shading devices, such as horizontally and vertically inclined louvres, movable screens, deciduous

trees and plants, can all be used to control direct solar radiation. The effectiveness of sunshades is poor, there- fore windows should be provided only in those positions where effective protection against the sun can be en- sured. Protection [1,6] against diffused and reflected radiation cannot be provided by any simple method.

Shading is the easiest to provide on the south wall where a horizontal projection at an appropriate height will exclude summer sun while permitting sunlight in the buildings in winter. The east and west walls can be protected by a combination of horizontal and vertical louvres, but fixed shading devices of this kind cannot be designed to allow sunlight in winter. In the case of Raja mahal, small windows on the first floor have been provided. These windows have a small area towards the inside, compared to the area towards the outside.

They are inset in the thick stone wall thereby reducing the heat transmission to the interior in summer and the decrease of heat loss in winter. These windows do not interfere with nighttime radiative cooling [11]. On the east and west sides, surface shading can be provided

(5)

G.N. Tiwari et aL / Energy and Buildings 22 (1995) 91-99 95 1.0

0.8

E

.~ 0.6

8

• g 0.4

"d

t~

0.2

. . . ; ' ' 2 ' 0.0 2 4 6 8 10 12 1/, 1 18 20 2 21.

Time (hrs.)

Fig. 3. V a r i a t i o n o f solar intensity with t i m e of t h e day. --<>- T o t a l r a d i a t i o n on h o r i z o n t a l surface; ~ diffused r a d i a t i o n on h o r i z o n t a l surface; ~ total r a d i a t i o n o n s o u t h - e a s t surface; -A_ diffuse r a d i a t i o n o n s o u t h - e a s t surface.

as an integral part of the building element. External shading devices used on a building surface should not interfere with nighttime radiative cooling. This is par- ticularly important for the roof surface which is exposed to the cool night sky. A solid cover of concrete or galvanized iron sheets will shade the roof from solar radiation but it will not permit the roof to cool down by radiation to the night sky. An alternative method is to provide a cover of deciduous plants or creepers.

Because of leaf evaporation, the temperature of such a cover will be lower than air temperature, thus allowing effective radiant cooling and shading at the same time.

The reduction of interior solar heat gain in summer is provided by the shading of courtyard walls. The layout plan of the building is compact with very few openings other than the door. The heat loss in summer is enhanced by ventilation of the veranda, by evaporative cooling and sprinkling of water.

5. Thermal analysis

To formulate the energy balance equation for different components of the mahal under study, the following assumptions have been made:

• one-dimensional heat flow has been considered through the walls and roof;

there is no temperature gradient within the en- closure;

• the wind velocity through windows has been con- sidered to be a constant;

• there is a uniform water layer over the roof;

• the mahal is in a steady-state condition;

• the water and roof temperatures are almost the same owing to the thin layers;

• the heat flows through the partition roof and the ground floor have been considered to be in a steady- state condition.

Following Kaushik et al. [4] and Sodha et al. [2], energy balance equations for different components of the mahal are given in the following paragraphs.

(a)

Roof of the mahal

The rates of heat flux per square metre passing through the roof surface at x = 0 with (gunny bags) and without roof treatment are given by:

(i) roof with gunny bags -K1 0T1

x ~ O

= or/1 ( t ) -hc(Ta[~-o - T a ) - he(ra[~ = o - T . )

-h~(T~L,_ o - 7".) - e AR

=od,(t)-(h~+he+h~)(Tl~=o-T.)-e AR

(1) (ii) roof without gunny bags [3]

--1(10Tll = o d l ( t ) - h ( T a ~ = o - Z a ) - e A R ( 2 )

1._o

where h c = 2 . 8 + 3 V

he

( l w _ l a ]

h r = ¢ o [ ( T w + 2 7 3 ) 4 - (Tsky + 273)4]/(Tw - T,) h = 5 . 7 + 3 . 8 V

rsky = ( r . -- 12)

The rate of heat flux per square metre entering an inside enclosure through the roof is given by:

OT1 [

- K , -~- .=L =h,[Td~_L,- r , , ] (3) (b)

Exposed wall

The rates of heat flux per square metre through an exposed wall at x = 0 and

x=Lw

via conduction are given by:

(i) exposed wall surface

- K z OTz[ =od2(t)-h(T2~=o- T.)

(4a)

WL_o

(ii) first-floor enclosure

-K2 07"2 =h,[T2[~_L, - Tin]

- ~ x~Lw

(4b)

(iii) ground-floor enclosure -K2 0T2 =h,[Tz[,_L.- TRE]

- ~ x~tw

(4c)

(6)

96 G.N. Tiwari et al. / Energy and Buildings 22 (1995) 91-99

(c)

Unexposed wall (facing to lane)

The rates of heat flux per square metre, gain and loss, through unexposed walls are given by:

(i) first floor enclosure

-K3 ---~'*=L. aT31 =h,[T3~-L.-

(5b) (ii) ground floor enclosure

aT3[ =h~[r3~

--TRz] (5c)

- K 3 - ~ ,~ = L. =L.

(d)

First floor ceiling

The rate of heat flux per square metre from enclosure 1 to enclosure 2 and vice-versa is given by

Q12 = U ~ z ( T R 1 - TR2) (6)

where

U I 2 = -[- Kll -[-

(e) Ground floor

The rate of heat flux per square metre lost to the ground is given by

Qb = Ub(TR2-- T . ) (7)

where Ub = 1 +

and T= is the temperature within the ground at large distances and it can be considered as the average temperature within the ground at a distance of about one metre.

The temperature distribution in the roof and walls can be obtained by solving the following one-dimensional heat conduction equation:

OZT OT

Ki - ~ = piCi -~

(8)

The solution of Eq. (8) (~), in a periodic condition can be written as [12]:

Tj =A?c + Bj + ~ [C.j

exp(/3n?c)

n ~ l

+D.j e x p ( -

~nix)]

exp(in~) (9) where

/3nj = + aj(n)'/2(1 +i)

= ( o, p j C / 2 K #

and Aj, Bj, C,~ and D,j are constants, which can be obtained by using the above boundary conditions, Eqs.

(1)-(7), where j = 1, 2, and 3 refer to roof, exposed and unexposed walls, respectively.

Now the energy balance equations for enclosure 1 (first floor) and enclosure 2 (ground floor) can be written as:

Aahi[ T,[~=c. - Tall + Aw2h,[ Tz~= tw

- TR,]

+Aw3h~[T3~,=L. - Tin]

dTR1

=MmCR, ~ + h I a A , I ( T R I - r , 1 ) -t" V o

+ V~(Tm - T.) + URAR(TR1 --

TRe) (10) and

URA (T I -

dTR2

+A,,,3hi[T3[~=Lw -

TRz] =MR2CR2 d---~

+h,2A,2(TR2 -

TI2) + Ub(TR2-- T) (11) where the expressions for Vo and Va can be obtained as given by Shaviv and Shaviv [8].

Further, the energy balance equations for isothermal mass for enclosures 1 and 2 are given by:

dT,1

h,1A,I(TR,

--

Tn) =MnCn

d--t- (12) and

dTIz

hI2A~2(TR2-

Tn)

=MI2C~2 dt

(13)

Since solar intensity

(I~(t))

and ambient air temper- ature

(Ta(t))

are periodic in nature, they can be ex- pressed in Fourier series [13]:

lj(t) =Ioj+ ~ I.j

exp

i ( n ~ - ~ ) (14a)

n = l

and

T,(t) = T~o+ ~ T~

exp

i(nwt-trn)

(14b) It is observed that up to six harmonics of these series give close representation of hourly variation of solar intensity and ambient air temperature and hence only six harmonics have been considered for numerical com- putations. Furthermore, the enclosed room (TRj) and isothermal mass air temperature (T~i) have also been expressed as follows:

6

rr~ = Tl~o+ ~ Try. exp(in~t) (15a)

and

6

T~j= Tijo+ E T~jn exp(inwt) (15b)

(7)

G.N. Tiwari et a L I Energy and Buildings 22 (1995) 91--99 97 Table 1

Properties of materials

Material Temp. Thermal conductivity K Density p Specific heat C

(K) (W/m °C) (kg/m 3) (kJ/kg °C)

Limestone 100-300 1.26-1,33 2500 0.90

Sandstone 40 1.83 2160 0.71

2300

W o o d 30 0.055 140

Cement and mortar 1200 1.90 1500

Lime mortar 20 0.48 1440 0.84

Steel 7833 0.46 54 1.474

4 0

38

t ~ m p e r o t u r ¢ / ~ x x "

/ / I ~ 1

36

l

34

v 32 o (3. e~

E 3 0

E

o 28

g~

26

24

22

6

Fig. 4. Effect of ventilation on room air temperature.

j - . . . Without vcntltation First ftoor

With ventitotion Ground ftoor

I 118 I

12 24

Tirn¢ of the day (hours) ="

With the help of Eqs. (14) and (15), Eqs. (1)-(13) give two matrices each for the time-independent and time-dependent parts. These matrices have been solved by the inverse matrix method by computational work to determine various constants including constants of enclosures 1 and 2, respectively. The results obtained are illustrated in Figs. 4 and 5.

6. Numerical results and discussion

In order to solve the matrix equation, the following design and climatic parameters have been used:

cr = 0.3, V = 2 m/s, e AR = 60 W / m 2, hc = 8.8 W/m 2 °C, h = 1 3 . 3 W/m 2 °C, hi=5.7 W/m 2 °C, h~=h2=5.7 W/m 2

°C, T=25 °C, Lm = L R 2 = 0 - 5 m. The properties of the materials are given in Table 1. The dimensions of the mahal are given in Fig. 2(a) and (b). The hourly

variations of beam and diffuse radiation are given in Fig. 3.

The hourly variation of room temperatures of en- closure 1 (first floor) and enclosure 2 (ground floor) are shown in Fig. 4. From this Figure, it is clear that the room temperature of the ground floor which is used for storage purposes is significantly lower than the room temperature of the first floor, owing to the fact that the exposed surface area of the first floor is higher than the exposed surface area of the ground floor. The effect of ventilation has also been taken into account and it is observed that ventilation has more effect during sunless hours owing to lower wind tem- peratures. The wind temperature is also lowered by evaporation from the water surface.

The effects of roof thickness and wetted gunny bags on room air temperatures are shown in Fig. 5. It can be concluded that there is a phase shift of 12 hours

(8)

98 G.N. Tiwari et al. / Energy and Buildings 22 (1995) 91-99 3z~

d

g ~ Z<

27 . . . 1 ~ 6 ~2 ~8 2 j 4

Time of the doy (hours)

Fig. 5. Effect o f gunny bag on room air temperature. I - first floor w i t h o u t gunny bag; I I - first floor with gunny bag; I I I - ground floor w i t h gunny bag; I V - ground floor w i t h 0.40 m ceiling thickness.

for 0.40 m roof thickness and also there is a further reduction in room air temperature owing to the large thermal capacity of the room material. T h e r e is also a significant reduction in room air temperature owing to evaporation over the roof surface. Most of the solar radiation is cut-off from the roof surface by the presence of gunny bags.

7 . C o n c l u s i o n s

On the basis of numerical performance and the study of the building, it is concluded that:

(i) T h e r e is a reasonable natural thermal comfort inside various rooms of a Raja mahal owing to the higher plinth level from the water level of the River Ganges which is generally not the case for contemporary building.

(ii) An arrangement for evaporative cooling should be incorporated in the existing structure from a thermal comfort point of view. H e r e plenty of water is available in the river even in summer. Water is not available for evaporative cooling in most of India in summer.

Hence there is no need for re-structure of the existing energy-efficient building from an economical point of view.

N o m e n c l a t u r e

All AI2 AR

surface area of isothermal mass 1 (m 2) surface area of isothermal mass 2 (m 2) surface area of roof between 1st and 2nd floor and ground floor(m 2)

mw2

Aw3

G

CI1 Ct2 CR1 CR2 h h~

h~

hi

hr

h12

hi

11 12

surface area of exposed wall for 1st floor

(m 2)

surface area of unexposed wall for 1st floor and ground floor (m 2)

specific heat o f j t h ,roof material (J/kg °C) specific heat of 1st isothermal mass (J/kg

°C)

specific heat of 2nd isothermal mass (J/kg

°C)

specific heat of room air of enclosure 1 (J/kg °C)

specific heat of room air of enclosure 2 (J/kg °C)

convective and radiative heat transfer coef- ficient from the roof to ambient (W/m 2 °C) convective heat transfer coefficient from roof to ambient (W/m z °C)

evaporative heat transfer coefficient for wetted roof (W/m 2 °C)

convective heat transfer coefficient from inner surface of roof/walls to enclosed room (W/m 2 °C)

radiative heat transfer coefficient from roof to sky (W/m: °C)

convective heat transfer coefficient from enclosed room 1 to isothermal mass 1 (W!

m 2 °C)

convective heat transfer coefficient from enclosed room 2 to isothermal mass 2 (W/

m 2 °C)

convective heat transfer coefficient from enclosed room 1 to first floor ceiling (W/

m 2 °C)

solar intensity on the roof (W/m 2) solar intensity on exposed wall (W/m 2)

(9)

G.N. Tiwari et aL / Energy and Buildings 22 (1995) 91-99 99

G Kj

K1

K~

K~

Z g L R

Lw

LR2 - - L R 1

MII M~2

MR1 MR2

P~

P.

t

T

T~

T~

T.

T,2

T~2

Tsky

T1

T~

T~

u~

uR(= G~)

V

Vo

thermal conductivity of the ground (W/m 2

°C)

thermal conductivity of thejth roof material (W/m 2 °C)

thermal conductivity of first floor roof ma- terial (W/m 2 °C)

thermal conductivity of the exposed wall material (W/m 2 °C)

thermal conductivity of the unexposed wall material (W/m 2 °C)

thickness of ground material (m) thickness of exposed roof (m) thickness of first floor roof (m) thickness of walls (m)

mass of isothermal mass 1 (kg) mass of isothermal mass 2 (kg) mass of room air of enclosure 1 (kg) mass of room air of enclosure 2 (kg) partial vapour pressure at ambient tem- perature (N/m 2)

partial vapour pressure at water temper- ature (N/m 2)

time coordinate(s)

temperature distribution of the roof (°C) ambient air temperature (°C)

galley temperature (°C)

temperature of isothermal mass 1 (°C) temperature of isothermal mass 2 (°C) temperature of room air of enclosure 1

(oc)

temperature of room air of enclosure 2

(oc)

sky temperature (°C) roof temperature (°C)

temperature of exposed wall (°C) temperature of unexposed wall (°C) ground temperature (°C)

bottom heat loss coefficient from 2nd floor to the ground (W/m 2 °C)

overall heat loss coefficient from enclosure 1 to enclosure 2 (W/m 2 °C)

wind velocity (m/s)

constant due to infiltration

v,

x

constant due to ventilation position coordinate

Greek letters

Ol E O"

AR

absorptivity emissivity

Stefan-Boltzmann constant, 5.67051 × 10-8

W m - 2 K - 4 .

phase change

density of roof/wall material (kg/m 3) long-wave radiation exchange between roof surface and sky

References

[1] M.S. Sodha, Solar Passive Buildings, Science and Design, Per- gamon, New York, 1986.

[2] S.C. Kaushick, G.N. Tiwari and J.K. Nayak, Thermal Control in Passive Solar Buildings, Geo-Environ Academia, Jodhpur, India, 1988.

[3] G.N. Tiwari, A. Kumar and M.S. Sodha, Cooling by water evaporation over the roof, Energy Convers. Manage., 22 (1982) 143.

[4] M.S. Sodha, A.K. Khatri and M.A.S. Malllck, Reduction of heat flux through a roof by water film, Solar Energy, 20 (1978) 189.

[5] B. Giovni, Passive cooling of building by natural energies, Energy Build., 2 (1979) 279.

[6] V. Loftness, The future of mud -- Passive Residential Design Competition, Proc. 3rd National Passive Solar Conf., Newark, DE, 1979, Vol. 3, ISES, p. 22.

[7] J. Paul, Passive Solar Design and Materials, Nayes Beta Corp., Park Ridge, USA, 1979.

[8] E. Shaviv and G.A. Shaviv, A model for predicting thermal performance of buildings, Worla'ngPapersASDM-8, Architectural Science and Design Methods, 1979.

[91 H. Sewey, Indian merchants in traditional selling Banaras, 1780-1820, The Imperial Impact, Home Press, 1978.

[10] K.P. Mishia, Banaras in Transition, 1738-1795, Munshiram Manohartal, New Delhi, 1975.

[111 T. Johnson, Preliminary performance of solar buildings, Proc.

2nd National Passive Solar Conf., Newark, DE, 1978, Vol. 1, ISES, p. 67.

[12] J.K. Threlkeld, Thermal Environment Engineering, PrenticeHall, Eaglewood Cliffs, NJ, 1970.

[13] G.N. Tiwari, U. Singh and J.K. Nayak, Applied Solar Thermal Energy Devices, Kamala Kuteer, West Godavari (AP), India,

1984.

References

Related documents

Concepts to design dyes in spectral sensitization 313 silver halide there may occur a spectrally sensitized luminescence of the silver halide by light excitation of

Digital Logic History - Gate

(a) passively-cooled building design that deploys natural and mechanical ventilation; (b) adoption of adaptive thermal comfort standards to specify pre-setting of temperatures of air

Consequently on the basis of simple pharmacokinetic concepts and parameters bioavailability and bioequivalence studies have been established as acceptable surrogates for

a) Engineering Details.. The type and characteristics of the glass used for the building has a profound effect on the indoor temperature. In order to help cooling the building

• Concepts:  Learning  computer  science  concepts that are generally useful in many  areas  as  well  as  some  concepts  that 

motivations, but must balance the multiple conflicting policies and regulations for both fossil fuels and renewables 87 ... In order to assess progress on just transition, we put

I hereby declare that the work presented in the thesis entitled ANALYSIS OF BUILDING FORM, PASSIVE HEATING AND HYPOCAUST CONCEPT FOR BUILDING DESIGN being submitted to the

The relative study of roof with different passive cooling concepts viz, vegetable pergola, roof garden /water-film, removable. canvas and inverted earthen pots, has also

Mathematical models have also been developed for the thermal performance of condenser which have been integrated with the cooling tower models to incorporate the above

The active heating concept with sensible heat storage materials such as water or rocks was investigated to analyse the storage effect of water mass, collector area and void

The concepts of dense gas formulation havo been applied to calculate the thermodynamic equilibrium properties namely the thermal expansion coefficient, compressibility

Similarly, mission automation concepts have been added for various operations with known timelines such as performing Mars Orbiter Insertion operation through an

The measurement and analysis of variability in sedi- ment flux and the interpretation of geomorphic processes has given rise to new concepts, namely nonlinearity (nonlinear

The analysis of the building has been made in terms of energy conservation due to various passive cooling concepts, namely; wind tower, earth air tunnel and

The performance of Building integrated Semitransparent Photovoltaic Thermal (BiSPVT) system have been analyzed in four cases, namely (A) Energy and exergy analysis of

The architects and planners face numerous problems for designing thermally comfortable buildings due to diverse nature of parameters constituting the weather. The problems are

Experiments have been conducted at Solar Energy Park, Indian Institute of Technology, Delhi, India for a passive house coupled with an earth-air heat exchanger. The passive house

Various digital and optical techniques [Javidi 2005] have been proposed for image encryption, based on various concepts such as chaotic maps, double random phase encoding

the glazing and the blackened surface of the wall. During night time, however the vents and closed to stop the air circulation. Periodic theory has been applied to analyse such

general, this thesis is a mixture of theretical and experi- mental work on 'Thermal Trap Flat Plate Solar pA2,4r4y Ccal&amp;ctor' and an analytical study of new passive concepts

This thesis presents some thermodynamic and heat transfer studies on solar space conditioning systems. Both active and passive methods of cooling have been proposed and